Water usage effectiveness

From Wikipedia, the free encyclopedia

Water Usage Effectiveness (WUE) is a sustainability metric created by The Green Grid in 2011 to measure the amount of water used by datacenters to cool their IT assets.[1][2]

Definition

[edit]

The unit is ,[3] or, equivalently, .[4]

The standard ISO/IEC 30134-9:2022[5] gives more context for accurate measure, as well as specific WUE categories and various WUE derivatives.

Typical values

[edit]

The WUE is a positive number. It can be 0 L/kWh (with air cooling) or up to 2.5 L/kWh (with evaporative cooling).[4]

Facebook published a WUE of 0.22 L/kWh for their datacenter of Prineville, Oregon for the second quarter of 2012.[2]

For the year 2025 Equinix reports a global WUE of 0.91 L/kWh for all their datacenters, and a WUE of 1.41 L/kWh for sites using evaporative cooling.[6]

Other metrics

[edit]

WUE is less widespread than the Power usage effectiveness (PUE), but is becoming more publicized by data center operators due to ESG considerations and/or due to water scarcity.[4]

According to Equinix,[4] PUE and WUE are partially opposites: with evaporative cooling the WUE increases and the PUE decreases, and with air cooling the WUE decreases (or is zero) but the PUE increases. The cooling technology of a given datacenter may be dependent on the region (and other considerations), and may be a mix of different technologies, possibly activated differently depending on the season.

See also

[edit]

References

[edit]
  1. ↑ "'Green Grid 'WP#35-Water Usage Effectiveness (WUE™): A Green Grid Data Center Sustainability Metric', retrieved 4 September 2015". Archived from the original on 9 May 2015. Retrieved 4 September 2015.
  2. 1 2 DataCenterKnowledge.com, Data Center Water Use Moves to the Forefront, retrieved 4 September 2015
  3. ↑ "WUE (water usage effectiveness) definition". Archived from the original on 6 September 2015.
  4. 1 2 3 4 "What Is Water Usage Effectiveness (WUE) in Data Centers?". Retrieved 13 November 2024.
  5. ↑ "ISO/IEC 30134-9:2022 Information technology — Data centres key performance indicators — Part 9: Water usage effectiveness (WUE)". 2022-03-01. Retrieved 2026-07-31.
  6. ↑ Equinix (2025). Sustainability Report 2025 (PDF) (Report). p. 26. Retrieved 2026-07-31.