Values do not seem reasonable

[edit]

Consider:

"Acceptable insulator resistance values are typically 1 to 10 megohm"

Really? Isn't it more like 1 to 10 gigohm or 1 to 10 teraohm? --Mortense (talk) 16:19, 5 August 2015 (UTC)Reply

Also the test voltage of 550 volts for a 440 volt circuit is nonsense. The [DC] test voltage needs to be significantly higher than the peak [AC] circuit voltage (which for a 440 volt circuit is 622 volts). The UK wiring regulations require a test voltage of 1500 volts on a 415 volt circuit. 109.152.208.48 (talk) 17:44, 12 January 2020 (UTC)Reply

Maybe this is an old one, like vintage? :)

[edit]

Newer Meggers go up to 1Gohm and further  Preceding unsigned comment added by 79.76.103.246 (talk) 12:42, 19 November 2016 (UTC)Reply


Megger is a Manufacturer, not an Equipment

[edit]

I am still impressed about this. I will correct this in the next time.Hyprwfrcp (talk) 23:50, 31 October 2019 (UTC)Reply