From Wikipedia, the free encyclopedia
(Redirected from Earthing transformer)
A grounding transformer

A grounding transformer or earthing transformer is a type of auxiliary transformer used in three-phase electric power systems to provide a ground path to either an ungrounded wye or a delta-connected system.[1][2] Grounding transformers are part of an earthing system of the network. They let three-phase (delta connected) systems accommodate phase-to-neutral loads by providing a return path for current to a neutral.

Grounding transformers are typically used to:

  • Provide a relatively low-impedance path to ground, thereby maintaining the system neutral at or near ground potential.[3]
  • Limit the magnitude of transient over voltages when restriking ground faults occur.
  • Provide a source of ground fault current during line-to-ground faults.
  • Permit the connection of phase-to-neutral loads when desired.[2]
Earthing transformer with a zig-zag

Grounding transformers most commonly incorporate a single winding transformer with a zigzag winding configuration, but may also be created with a (rare case) delta-wye transformer.[2][4] Neutral grounding transformers are very common on generators in power plants and wind farms.[2] Neutral grounding transformers are sometimes applied on high-voltage (sub-transmission) systems, such as at 33 kV, where the circuit would otherwise not have a ground; for example, if a system is fed by a delta-connected transformer. The grounding point of the transformer may be connected through a resistor or arc suppression coil to limit the fault current on the system in the event of a line-to-ground fault. [5]

References

[edit]
  1. ↑ "Grounding Transformer" (PDF). Swedish Neutral.
  2. 1 2 3 4 Dickinson, Mike (August 19, 2011). "Grounding Transformers". Pacific Crest Transformers. Retrieved September 4, 2017.
  3. ↑ "Floating Neutral Transformer". Neutral Transformers. 14 August 2021.
  4. ↑ "Grounding Transformer FAQs". Pacific Crest Transformers. November 8, 2013. Archived from the original on August 13, 2018. Retrieved September 4, 2017.
  5. ↑ Martin Heathcote (ed.), J & P Transformer Book, Newnes, 2011 ISBN 0080551785pp. 421-422